WEFLO Y-Type Strainer, Grooved Ends, FIG.F0522-175
Specification :
- Meet or exceed the requirements of UL 321 Standard.
- NPT or BSPT blowoff outlet on cover (blowoff outlets are furnished with plugs).
- Recessed seat in body assures accurate screen alignment Round holes with 60 degrees staggered.
- Excellent flow characteristics and low pressure losses at high flow rates.
- Grooved Connections are cut in accordance with AWWA C 606 or other standard Groove Specifications for Steel Pipe.
- Rated Working Pressure 175 psi.
- UL 321 / ULC Listed.
Description
Reviews (0)
Be the first to review “WEFLO Y-Type Strainer, Grooved Ends, FIG.F0522-175” Cancel reply
Shipping & Delivery
Related products
WEFLO Water Motor and Gong, FIG.WMA-16
Operation :
When a Deluge Valve is activated, water flows through the valve's trim, discharges to a strainer and into the water motor inlet, From the inlet, the water flows through a nozzle which directs the stream to the impeller. The stream turns the Impeller and drive shaft, causing the striker arm to rotate, thus producing a continuous alarm. The water is discharged thro-ugh a 1"(25mm) drain outlet at the bottom of the impeller ho-using. The discharged water must be piped through the wall to a suitable open drain.
WEFLO Automatic Sprinklers
Specifications:
Style: Pendent, Upright, Sidewall
Minimum Operating Pressure: 7 psi(0.5 bar)Maximum
Working Pressure:175 psi(12 bar)
Factory tested hydrostatically to 500 psi(34.5 bar)
Thread Size: ½" NPT, 15 mm BSPT
Nominal K-Factor: 5.6 U.S.(80.6 metric*)
Overall Length: 2-3/8”(60 mm)
Finish : Brass, Chrome Plated and White Polyester Available
Metric K-factor measurement shown is in Bar.
When pressure is measured in kPa.
divide the metric K-factor shown by 10.0.
WEFLO Platform Fire Hydrant U246C
Specifications :
Meet or Exceed the Requirements of UL 246C Standard.
NFPA 1963 Standard Nozzle Threads.
Bronze Body and Hose Nozzle.
0-ring Sealed Stem Nut and Hose Nozzle.
Excellent Flow Characteristics.
Multiple Nozzle Configurations.
Monitor Style available.
UL246C Listed, FM Approved.
250 psi Maximum Working Pressure.
WEFLO Vane-Type Waterflow Detector GIF.F6001S
Features :
- Equipped with tamper resistant screws to prevent unauthorized entry.
- The F6001S fits 1", 1%",1%", and 2" brass and copper threaded tees, in addition to 1 "and 1½" CPVC tees.
- Clearly marked plastic paddles are included to fit the different installation configurations.
- One switch is enclosed in the detector.
- Terminals are easy to read and wire.
- Designed and built for accuracy and repeatability.
- Rated Working Pressure: 300 psi.
- Flow Sensitivity Range for Signal: 15-37.8 L/min (4-10GPM)
- Contact Ratings: 8Aat125/250VAC, 3Aat 24VDC.
- Maximum Surge: 18 FPS (5.5m/s)
- UL/ULC Listed
- EAC and CE Certified.
WEFLO Explosion-Proof Vane-Type Waterflow Detector FIG.F6001EX
Specifications :
- Designed and approved to operate in hazardous locations.
- Two synchronized switches are enclosed outside of explosion environment.
- Terminals are easy to read and wire.
- Built-In mechanical time delay feature; minimizing the risk of false alarms due to pressure surges or air trapped in the system.
- Offers excellent performance during riser vibrations caused by large in-rushes of water.
- Designed and built for accuracy and repeatability.
- Hazardous Atmosphere Classification: Class I: Div. 1. Groups C, D T6; Class I: Div.2,Groups C,D T6; Class II: Div.1,Groups E,FG T6; Class II: Div.2,Groups F GT6: Class III. DNV 22 ATEX 17663X; IECEx DNV 22.0041X; Ex db lB T6 Gb; Ex tb llC T8O'c Db Ip66
- Maximum pressure:
- Flow sensitivity range
- Contact rating
- Maximum Surge: 18FPS (5.5m/s)
- Entry Size: 1/2"NPT threaded conduit connections
- NEMA 4/ P66 Rated enclosure rating
- Ambient Temperature: 0'C to 49C
WEFLO Plug Type Supervisory Switch
Features
e Dimensions: 18 cmx 10 cm x7cm
Weight: 380g
Enclosure: Non-Corrosive Composite Material.
Temperature Range: -40°C to 60°C
Housing Cover Tamper: Activated by housing cover removal.
Contact Ratings: SPDT Plug Contacts:100 mA@ 28 VDC/AC250 mA @ 12 VDC/AC
Cable:2-wire,18 Ga.Waterproof-Approx.8'(2.43m)long.
Fine adjustment feature for fast, easy installation.
.UL/ULC Listed, FM Approved
WEFLO Adjustable Wall Indicator Post FIG.F0800-WP
Specifications:
- Meets or Exceeds the Requirements of NFPA 24 Standard.
- Indicate if the Post Indicator Valve is OPEN or SHUT.
- Target Nut Allows 13 to 45 Turns to Open (3"-14" Valve size).
- Viewing Windows are Polycarbonate with UV Resistance.
- Stem Telescopes to Required Length, no cutting necessary.
- OPEN / SHUT targets are Easily Adjustable.
- UL/ULC 789 Listed, FM 1110 Approved.
- CNBOP Certified.
- RAL 3000 Safety Red Lined / Coated.
WEFLO Dry-Barrel Fire Hydrant FIG.F0733-250
Specifications:
Meet or Exceed the Requirements of AWWA C502 Standard.
NFPA1963 Standard Nozzle Threads.
Traffic Feature with Duplex Stainless Steel Safety Stem Coupling, Excellent Flow Characteristics.
Multiple Nozzle Configurations.
Mechanical Joint Base Elbow.
Dry Top Design with O-ring Sealed Oil Reservoir.
Dual Auto-frost Bronze Drain Valves as Standard
UL246 Listed and FM 1510 Approved. Rated Working Pressure 250 psi. Certified to NSF/ANSI61&372
Reviews